Laminar systems for operating rooms 

Ceiling systems MLS for operating rooms are an element of clean rooms and are designed to prevent infection in the wound (during surgical operations) by feeding a laminar (low-turbulent) sterile air flow at a certain rate (0.24-0.3 m / s) in the operating field. High-efficiency air HEPA filters of class H14 are used for air purification. This complex of measures makes it possible to reduce the likelihood of postoperative complications, to shorten the period of recovery of the patient after the operation and, as a consequence, to reduce the costs for the patient's stay in the medical institution.

 

 

Materials:

  • MLS-SS: polished stainless steel grade AISI 304 "2B"
  • MLS-PS: powder-coated steel

The housing of the ceiling system has flat, smooth surfaces that are easily cleaned. Outside, the housing is covered with a material that absorbs noise from the ventilation system. The ceiling system has perforated laminating machines, which are quickly removed, as well as a simple and reliable design of the filter fasteners, which simplifies maintenance.

atr.
MLS-
SS

art.
MLS-
PS

type

А,
mm

В,
mm

С,
mm

С/2,
mm

D,
mm

E,
mm

F,
mm

G,
mm

Weight,
kg

air consumption,
m3/hour

air consumption,
m3/s x10-3

8.1.1 8.2.1 14/20 1350 1940 1800 930,5 610 1271 1861 800 140 1700 472
8.1.2 8.2.2 14/25 1350 2600 2276 1245,5 610 1271 2491 900 185 2350 662
8.1.3 8.2.3 20/20 1990 1940 1800 930,5 1250 1911 1861 800 210 2700 750
8.1.4 8.2.4 20/25 1990 2570 2491 1245,5 1250 1911 2276 900 270 3700 1028
8.1.5 8.2.5 20/32 1990 3208 3129 1564,5 1250 1911 3000 1300 335 4700 1300
8.1.6 8.2.6 25/25 2600 2600 2276 1245,5 1860 2521 2491 900 342 4850 1400
8.1.7 8.2.7 25/32 2600 3210 3000 1564,5 1860 2521 3129 1300 394 8220 2270